Calculate NPSHA for centrifugal pumps.

Assess suction conditions for water: account for surface pressure, liquid level, vapour pressure and suction line losses together.

Use a decimal comma or point, without thousands separators. Changing units converts the input value.

Water and installation location
Calculator scope: pure water from 1 to 95 °C.
Standard atmosphere, −500 to 5,000 m; weather-related pressure variations are not included.
Positive: level above pump. Negative: pump above level. For horizontal pumps.
Pressure above the liquid surface
Suction line losses
Known suction line loss
Include inlet and fittings; do not add elevation again.
Pipe and flow data
Reference value for new steel pipe; consider actual material and condition.
1.004 approximately applies to water at 20 °C. Enter the appropriate property at other temperatures.
Inlet, bends, valves, filters, etc., from geometry or manufacturer data; referenced to the entered pipe velocity.
Only losses not already included in pipe friction or ΣK.
Comparison with the pump
From the manufacturer's curve at the duty point under consideration.
Example value, not a universal safety requirement.
Both margins are checked simultaneously. Agree them with the manufacturer.

Distinguishing NPSHA from NPSH3

NPSHA is the head above vapour pressure provided by the system at the pump inlet. NPSH3 is pump-specific: the NPSH at which cavitation causes a 3% head drop. NPSHA exceeding NPSH3 therefore does not automatically mean cavitation-free operation.

NPSHA = (psurface,abs − pvapour) / (ρ · g) + z − hL

The balance starts at the stationary surface of a large tank. z is referenced to a horizontal pump's axis. Surface velocity is neglected. Pump inlet velocity head is not subtracted again in this tank-based balance. All pipe, inlet and fitting losses up to the pump inlet belong to hL.

Suction line losses

hL = (f · L/D + ΣK) · v²/(2g) + hadditional
v = 4Q/(πD²) ··· Re = vD/ν

The calculator uses the Darcy friction factor: 64/Re up to Re = 2,000, iteratively solved Colebrook above Re = 4,000, and linear interpolation between the boundary values. The transition region is uncertain. A constant internal pipe diameter is assumed; for multiple diameters, calculate section losses separately and enter their total.

Local loss coefficients are entered as a sum. This accounts for actual fittings and installation conditions rather than deriving generic values solely from the number of components.

Water properties, atmospheric pressure and margins

Vapour pressure and approximate liquid density use the IAPWS SR1-86(1992) saturation equations. Pressure effects on density are neglected. Kinematic viscosity is entered separately. The model is not intended for mixtures, gas-laden or highly viscous media.

Local atmospheric pressure uses p = 101,325 · (1 − 0.0065 · h / 288.15)5,25588 Pa. For a closed tank, surface pressure can be specified as absolute or relative to this calculated atmospheric pressure.

The example margins of 0.6 m and 1.25 are adjustable. The calculated NPSH3 limit is min(NPSHA − absolute margin; NPSHA / minimum ratio). A negative limit means no positive NPSH3 can satisfy these criteria. Required margins depend on the pump manufacturer, application and operating range.

Calculation references

These calculators support preliminary engineering sizing. Check the suitability of assumptions and results for the specific application. They do not replace complete pump, system or drive design.